16A / 32A / 63A / 125A: how to pick the rating in three steps
The rating follows the equipment current with at least 20% headroom: 16A ≈ 7.5kW, 32A ≈ 15kW, 63A ≈ 30kW, 125A ≈ 60kW (three-phase 380V). With the conversion formulas and the four commonest mistakes.
Conclusion: the rating is decided by one thing — the rated current of the equipment — with at least 20% headroom. The usual ratings (estimated for three-phase 380V):
| Rating | Roughly carries | Typical use | Models we stock |
|---|---|---|---|
| 16A | up to ≈ 7.5kW | Small machine tools, pumps, fans, workstation power | 745 |
| 32A | up to ≈ 15kW | Medium machinery, welders, packaging machines, cold stores | 569 |
| 63A | up to ≈ 30kW | Larger machinery, temporary distribution, container socket boxes | 201 |
| 125A | up to ≈ 60kW | Main feeds, large machinery, site distribution | 79 (mostly IP67) |
Estimated at three-phase 380V and power factor 0.85, already allowing for "continuous current ≤ 80% of rating". Motor loads also need starting current considered.
Three steps
- Work out the current: the nameplate rating is best; if you only have power, convert with the formulas below and round up to the next standard rating (16 / 32 / 63 / 125A).
- Then the poles: is a neutral needed? Three-phase with neutral = 5-pole (3P+N+earth), three-phase without = 4-pole (3P+earth), single-phase = 3-pole (2P+earth). See counting poles.
- Finally mounting and IP rating: wall (wall-mounted) / equipment panel (add-on = panel-mounted = flush) / cable end (connector); IP44 is enough in a dry workshop, outdoors, wash-down and cold stores need IP67.
Power to current (quick field estimate)
| Supply | Formula | Quick rule |
|---|---|---|
| Three-phase 380V | I = P ÷ (√3 × 380 × 0.85) | current A ≈ kW × 1.8 |
| Single-phase 220V | I = P ÷ (220 × 0.85) | current A ≈ kW × 5.4 |
Examples: 11kW three-phase motor → 11 × 1.8 ≈ 20A → take the 32A rating (16A is not enough); 5.5kW three-phase pump → ≈ 10A → 16A is enough (still leave headroom for a motor); single-phase 3kW heater → 3 × 5.4 ≈ 16A → right at the 16A limit, going to 32A is safer.
What each rating looks like in our stock
| Rating | Commonest poles | Commonest IP rating |
|---|---|---|
| 16A | 3 / 4 / 5-pole all available (including SCHUKO and low voltage) | Mostly IP44, IP67 also stocked |
| 32A | Mostly 4 / 5-pole | About half IP44, half IP67 |
| 63A | 4 / 5-pole | Mostly IP67 |
| 125A | 4 / 5-pole | Almost all IP67 |
The four mistakes people make
- Copying the old plug instead of reading the equipment current — the machine was upgraded, the cable was not, and that is a latent fault.
- No headroom: a 16A device run at 16A continuously heats the terminals and shortens life. 20% is the minimum.
- Looking at current only: 32A comes in both 4-pole and 5-pole variants (see 93xx cross-reference) and the wrong one will not fit.
- Ignoring cable size and terminals above 63A: 125A has requirements for conductor cross-section and terminal torque — confirm the cable at the same time.