Home › Selection guide › Reefer container sockets: 32A 380-440V 4-pole IP67, clock position 3h

Reefer container sockets: 32A 380-440V 4-pole IP67, clock position 3h

Reefer power is its own specification: 32A, 380-440V, 4-pole (3P+earth), IP67, and clock position 3h — which does not mate with a standard 400V 4-pole 6h. Sockets, plugs, connectors, phase sequence testing and interlocks, with item numbers.

Start with the conclusion: reefers have their own specification — 32A, 380-440V, 4-pole (3P + earth), IP67, and the clock position is 3h.

The critical point: a standard 400V 4-pole device uses clock position 6h (e.g. 9372), while reefer equipment uses 3h. A different clock position means it physically will not mate. So a standard 400V socket must not be used to power a reefer — that is both what the standard requires and what stops a reefer being plugged into an ordinary circuit.

Why the 3h position exists

IEC 60309-2 allocates clock positions by voltage and application, as mistake-proofing. Within the 380-440V band, reefers use 3h so they are distinct from the 6h used by ordinary industrial circuits: ports, yards and cold stores have both, and the clock position prevents cross-plugging. For the full picture on clock positions and poles see counting poles and interchangeability.

What a complete reefer supply needs (with our models)

PartNotesOur models
Socket (fixed end)Mounted on the yard pillar or wall; 32A 380-440V 4-pole IP67 9562 wall-mounted socket
2123A panel-mounted socket
Switched / interlockedCannot be unplugged live: switch off first, protecting both the operator and the compressor 5946A wall-mounted socket (switch + DUO mechanical interlock)
5792A switch + DUO interlock + DIN rail
Plug (cable end)Fitted to the reefer supply cable 2175B AM-TOP plug
2600 PowerTOP plug
ConnectorPortable (female) for cable extension 2177A AM-TOP connector
Appliance inletMounted on the enclosure, cable enters from outside 2692 appliance inlet
Phase sequence testerEssential: reversed phase sequence makes the compressor run backwards and can destroy it 3718 phase sequence test plug (32A 380-440V 4-pole)
Protective coverDust and water protection, and prevents touching, when nothing is plugged in 41342 (for 32A 4p plugs)
40841
Combination unitCEE socket + DUO interlock + SCHUKO + 3× MCB 32A, 520×225 mm enclosure 940027 reefer combination unit

Three things that matter on site

  1. Phase sequence: reefer compressors are sensitive to it and run backwards if reversed. Fit a phase sequence test plug or check with a phase meter before energising — this step saves the cost of a compressor.
  2. Plugging in live: at 32A an arc erodes the contacts. For yards and ports use switched + DUO mechanically interlocked sockets (5946A, 5792A): the plug cannot be removed until the switch is off.
  3. IP rating: open yards, wash-down and salt air require IP67 (IP44 is splash-proof only and is not suitable for wash-down or permanent outdoor use).

FAQ

Q: Can I power a reefer from an ordinary 32A 400V 4-pole socket?
A: Not advisable, and it usually will not fit — the clock positions differ (6h standard, 3h reefer), which is the mistake-proofing built into the standard. For an existing circuit, specify reefer-specific parts.

Q: Is 32A 4-pole enough to go on?
A: You also need to check the clock position, IP rating and whether it is switched/interlocked. "32A 4-pole" covers both 3h and 6h, which are different products.

Q: Must the plug and socket be bought as a pair?
A: Yes. The reefer usually already has its original cable and plug, so we match the socket to your existing plug (or a photo of it) to avoid getting the clock position wrong.

Port, yard and cold-store projects can be supplied as a complete set: socket + plug + phase sequence tester + protective cover + combination unit. Send a site photo or the model of your existing plug and we match by clock position, with product photos and datasheet PDFs. (We supply the full MENNEKES range, fixed and portable ends.)

Related: counting poles · can MENNEKES mate with domestic CEE? · IP44 vs IP67

Browse the reefer range: all reefer models.

Need a quote or selection advice?

Send us the model or site parameters — our engineers verify the specs and lead time, then quote.

Continue reading

How to choose industrial plugs and sockets: 5 steps to the right model
Current, poles, IP rating, mounting and brand — follow these five steps and you pick the right industrial plug or socket the first time, without trial and error.
IP44 vs IP67: what the two numbers really mean
The difference is not just a bit more water resistance. What IEC 60529 actually specifies, and how to choose for outdoor and wet areas.
Reading MENNEKES model numbers: 32xx / 27xxx / 13xA
How MENNEKES numbers its industrial plugs, sockets and connectors, and how to recognise a model at a glance.
Reading the MENNEKES 93xx series: 9322 / 9342 / 9372 / 9382 compared
93xx is the MENNEKES wall-mounted IP67 industrial socket series. The last digit gives the voltage, the third digit the poles and current. The full 9300–9382 table and the four comparisons people ask about most.
Can MENNEKES sockets be interchanged with other CEE brands? Check the clock position first
Interchangeability is not about the brand but four things: current, poles, clock position and IP rating. With the clock positions we verified against our own stock (110V = 4h, 230V single-phase = 6h, 400V 3-pole = 9h, 400V 4/5-pole = 6h, 500V = 7h).
Counting poles on industrial plugs and sockets: 3P / 4P / 5P explained
One model is written 3P on one page and "3-pole" on another — it is the same number, and the earth is always counted. With a table checked against the manufacturer datasheets (voltage and clock position included).
What people call industrial sockets: add-on = panel-mounted = flush-mounted
The same product has several names: add-on socket, panel-mounted socket and flush-mounted socket are the same thing, while wall-mounted is a different one. A full glossary so you quote the right model.
16A / 32A / 63A / 125A: how to pick the rating in three steps
The rating follows the equipment current with at least 20% headroom: 16A ≈ 7.5kW, 32A ≈ 15kW, 63A ≈ 30kW, 125A ≈ 60kW (three-phase 380V). With the conversion formulas and the four commonest mistakes.