Home › Industry solutions › Food and beverage plants: choosing industrial plugs and sockets for wash-down areas

Food and beverage plants: choosing industrial plugs and sockets for wash-down areas

Wash-down in food, beverage and central-kitchen areas means hot high-pressure water and detergent — even IP67 may not be enough. IP69 versus IP67, and how to specify for wash-down zones.

In food and beverage the difficulty is not the current, it is the cleaning: hot high-pressure water, foam detergent and sanitiser every day, which an ordinary splash-proof socket simply does not survive.

IP67 versus IP69

RatingWhat it withstandsTypical location
IP44Splashes from all directionsDry workshops, offices
IP67Short immersion (1 m for 30 min), dust-tightFloors after wash-down, outdoors, damp areas
IP69Close-range high-pressure, high-temperature water jets (80°C, 80–100 bar class)Food and beverage lines, central kitchens
Note: IP69 is not simply "a better IP67" — it is specifically about high-pressure, high-temperature jets. Wash-down zones in food plants should be specified to IP69 rather than pushed onto IP67.

Our IP67/IP69 models (stocked)

ModelSpecificationType
1363316A 500V 3-pole IP67/IP69PowerTOP® Xtra R plug (ErgoCONTACT)
1364216A 230V 5-pole IP67/IP69PowerTOP Xtra R plug
5602407G16A 500V 4-pole IP67/IP69Wall-mounted socket DUO (interlocked)
5604407G32A 500V 4-pole IP67/IP69Wall-mounted socket DUO (interlocked)

Three practices for wash-down zones

  1. Mount the socket above the wash surface and bring the cable in from below, so water cannot run down the cable into the mating face.
  2. Use covered or interlocked models: covered when nothing is plugged in, locked while it is — protection at both ends.
  3. Check the seal regularly: the IP rating lives in the seal; hardened, deformed or missing seals mean a downgrade.
Reference: the MENNEKES food industry solution.

Related: IP44 vs IP67 · how to count poles

Tell us the wash method (pressure and temperature), mounting position and load per circuit and we will specify a complete IP69 set. Contact our engineers

Need a quote or selection advice?

Send us the model or site parameters — our engineers verify the specs and lead time, then quote.

Continue reading

How to choose industrial plugs and sockets: 5 steps to the right model
Current, poles, IP rating, mounting and brand — follow these five steps and you pick the right industrial plug or socket the first time, without trial and error.
IP44 vs IP67: what the two numbers really mean
The difference is not just a bit more water resistance. What IEC 60529 actually specifies, and how to choose for outdoor and wet areas.
Reading MENNEKES model numbers: 32xx / 27xxx / 13xA
How MENNEKES numbers its industrial plugs, sockets and connectors, and how to recognise a model at a glance.
Reading the MENNEKES 93xx series: 9322 / 9342 / 9372 / 9382 compared
93xx is the MENNEKES wall-mounted IP67 industrial socket series. The last digit gives the voltage, the third digit the poles and current. The full 9300–9382 table and the four comparisons people ask about most.
Can MENNEKES sockets be interchanged with other CEE brands? Check the clock position first
Interchangeability is not about the brand but four things: current, poles, clock position and IP rating. With the clock positions we verified against our own stock (110V = 4h, 230V single-phase = 6h, 400V 3-pole = 9h, 400V 4/5-pole = 6h, 500V = 7h).
Counting poles on industrial plugs and sockets: 3P / 4P / 5P explained
One model is written 3P on one page and "3-pole" on another — it is the same number, and the earth is always counted. With a table checked against the manufacturer datasheets (voltage and clock position included).
What people call industrial sockets: add-on = panel-mounted = flush-mounted
The same product has several names: add-on socket, panel-mounted socket and flush-mounted socket are the same thing, while wall-mounted is a different one. A full glossary so you quote the right model.
16A / 32A / 63A / 125A: how to pick the rating in three steps
The rating follows the equipment current with at least 20% headroom: 16A ≈ 7.5kW, 32A ≈ 15kW, 63A ≈ 30kW, 125A ≈ 60kW (three-phase 380V). With the conversion formulas and the four commonest mistakes.